What are the recommended maximum fixing intervals for copper tube supports?

Copper Tube Diameter
mm
Intervals for Vertical runs
m
Intervals for Horizontal runs
m
6
0.6
0.3
8
0.9
0.6
10
1.2
0.8
12
1.5
1.0
15
1.8
1.2
22
2.4
1.8
28
2.4
1.8
35
3.0
2.4
42
3.0
2.4
54
3.0
2.7
67
3.6
3.0
76
3.6
3.0
108
3.6
3.0
133
3.6
3.0
159
4.2
3.6