FAQs
What are the recommended maximum fixing intervals for copper tube supports?
|
Copper Tube Diameter
mm |
Intervals for Vertical runs
m |
Intervals for Horizontal runs
m |
|
6
|
0.6
|
0.3
|
|
8
|
0.9
|
0.6
|
|
10
|
1.2
|
0.8
|
|
12
|
1.5
|
1.0
|
|
15
|
1.8
|
1.2
|
|
22
|
2.4
|
1.8
|
|
28
|
2.4
|
1.8
|
|
35
|
3.0
|
2.4
|
|
42
|
3.0
|
2.4
|
|
54
|
3.0
|
2.7
|
|
67
|
3.6
|
3.0
|
|
76
|
3.6
|
3.0
|
|
108
|
3.6
|
3.0
|
|
133
|
3.6
|
3.0
|
|
159
|
4.2
|
3.6
|